Lifebreath 195ECM Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Luftreiniger Lifebreath 195ECM herunter. Lifebreath 195ECM User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 1
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
49
"
(1245)
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
14 3/4"
(375)
19"
(483)
Ports
7" (178 mm)
CONDENSATE
DRAINS
BLOWERS
*NOTE: Front clearance of 25 inches (635 mm)
is recommended for servicing unit.
MOTOR
FRESH AIR
FROM OUTSIDE
STALE AIR
FROM INSIDE
FILTER
DEFROST
DAMPER
DEFROST AIR
FROM INSIDE
FILTER
Ports
6" (150 mm)
METAL CLASPS
ENGINEERING DA T A
THERMALLY CONDUCTIVE,PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. The two
cores are arranged for highly efficient counter current airflow.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common ECM motor. 5 speed
fan operation. 120 VAC, 1.4 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester
straps that are supplied with the unit.
DEFROST
Damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode (each mode has 5 speeds).
Control pad can be removed from HRV and remotely mounted.
Weight 106 lbs. (48 kg) Shipping Weight 108 lbs. (49 kg)
All units conform to
CSA and UL standards.
Model 195ECM
DIMENSIONS 195ECM inches (mm)
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs
Performance
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 171 (81)
@ 0.2" (50 Pa) 164 (77)
@ 0.3" (75 Pa) 156 (74)
@ 0.4" (100 Pa) 143 (67)
@ 0.5" (125 Pa) 134 (63)
@ 0.6" (150 Pa) 126 (59)
@ 0.7" (175 Pa) 119 (56)
Max. Temperature Recovery 88%
Sensible Effectiveness
@ 114 cfm (54 L/s) 32°F (0°C) 88%
*Sensible Efficiency
@ 114 cfm (54 L/s) 32°F (0°C) 81%
*Sensible Efficiency
@ 119 cfm (56 L/s) -13°F (-25°C) 77%
VAC @ 60HZ 120
WATTS / Low speed 34
WATTS / High speed 95
Amp rating 1.4
20
40
60
80
100
120
140
160
180
200
220
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Static Pressure (in w.g.)
Air Flow (cfm)
OPTIONAL MAIN CONTROLS
99-350 Lifestyle Ventilation Control 7/24 programmable ventilation, (3 wire) 20
gauge wire (min.) 100’ length
99-109 Air Sentry Air Quality Monitor designed to accept remotely mounted
Control Pad, (3 wire) 20 gauge wire (min.) 100’ length
99-250 Ventilation Dehumidistat designed to accept remotely mounted Control
Pad, (4 wire) 20 gauge wire (min.) 100’ length
OPTIONAL TIMERS
99-104 Digital Electronic Timer - initiates high speed ventilation for 20, 40 or 60
minutes, (3 wire) 20 gauge wire (min.) 100’ length
99-101 Crank Timer - Initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100’ length
OPTIONAL ACCESSORIES
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6” (150 mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6” (150 mm)
99-185 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core anda5yearreplacement
parts warranty.
The ECM motor produces a tone that some may
find objectionable. We recommend the
installation of the optional 99-SILENCER6 on the
‘Stale Air from Inside and ‘Fresh Air to Inside
ducts.
ATTENTION